Welcome Home Inspections Customer
 
Inspection Report
Welcome Home Inspections
Tyler Knelsen, C.E.T.
RR 2
Millet, Alberta T0C 1Z0

Phone: 780-628-4845
Cell: 780-387-1090
Email: tyler@welcomeinspections.com
Web: www.welcomeinspections.com
It has been a pleasure to provide your inspection service and we truly appreciate your patronage. We worked hard to research your real estate investment and report back to you in a comprehensive way to answer all of your questions as thoroughly as possible. Remember that we have your best interests in mind throughout this process and we are happy to answer any questions that you might have about the inspection. Please feel free to call us directly with any of your questions.
REPORT PREPARED FOR:
Sample Customer
INSPECTED PROPERTY ADDRESS:
Address
City AB Postal Code

Top Table of Contents Bottom
 

Table of Contents


Top Table of Contents Bottom
 
Date: 7/31/2008 Time: 10:00 AM Report ID: SampleReport1
Property:
Address
City AB Postal Code
Customer:
Sample Customer
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Age Of Home:
Over 25 Years

Client Is Present:
No

Radon Test:
No

Water Test:
No

Weather:
Clear

Temperature:
Over 20

Rain in last 3 days:
No

   
Top Table of Contents Bottom
Roof Covering:
Wood shakes
Viewed roof covering from:
Ladder
Binoculars
Sky Light(s):
None
Chimney (exterior):
Brick
Roof Structure:
Not visible
Roof-Type:
Gable
Method used to observe attic:
Inaccessible
Attic info:
Scuttle hole
 
Inspection Items
1.0 ROOF COVERINGS
Comments: Repair or Replace
There is a broken shake on the first story roof on the front of the house. There are also exposed roofing nails that should be sealed with roofing tar.  These defects should be inspected and repaired by a qualified contractor.
1.0 Picture 1 Broken shake
1.1 FLASHINGS
Comments: Repair or Replace
There is flashing missing between the roof and wall on the front of the house.  This can allow moisture intrusion and damage to the sheathing.  This should be inspected and repaired by a qualified contractor.
1.1 Picture 1
1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Comments: Repair or Replace
There is a hole cut in the chimney cap.  This should be inspected and repaired by a qualified contractor.

A stainless steel chase cover is recommended to prevent further deterioration to the chimney crown.  This should be installed by a qualified contractor.

1.2 Picture 1
1.3 ROOF DRAINAGE SYSTEMS
Comments: Inspected

(1) The downspouts discharge into an underground drainage system.  These drains should be monitored and kept free of debris to ensure proper drainage.
1.3 Picture 1

(2) The gutter is loose at the right corner (facing rear). Loose or leaking gutters can cause deterioration of fascia, soffit or roof edge. A qualified contractor should inspect and repair as needed.
1.3 Picture 2
1.4 ROOF STRUCTURE AND ATTIC
Comments: Not Inspected
Top Table of Contents Bottom
Siding Style:
Lap
Brick
Siding Material:
Vinyl
Brick veneer
Exterior Entry Doors:
Wood
Steel
Appurtenance:
Deck with steps
Covered porch
Sidewalk
Driveway:
Cobblestone
Gravel
 
Inspection Items
2.0 SIDING, FLASHING AND TRIM
Comments: Repair or Replace
(1) The area between the rear patio door and bricks needs to be re-caulked to prevent moisture intrusion.
2.0 Picture 1 Deteriorated caulking
(2) Weep holes were observed spaced throughout the bottom course of brick around the house. Ensure these holes always remain unobstructed to allow for moisture drainage.
2.0 Picture 2 Weep hole
2.1 EAVES, SOFFITS AND FASCIAS
Comments: Inspected
2.2 DOORS (Exterior)
Comments: Repair or Replace
(1) The rear entry door is torn or damaged. Further deterioration may occur if not repaired. I recommend repair as desired.
2.2 Picture 1 Damaged screen door
(2) The paint has pealed on the rear door to the garage and other exterior doors.  Recommend repainting.
2.2 Picture 2
2.3 WINDOWS
Comments: Repair or Replace
The paint and caulking around many of the windows is deteriorated.  The trim should be repainted and the edges re-caulked.
2.3 Picture 1
2.3 Picture 2
2.3 Picture 3
2.4 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS
Comments: Repair or Replace
There is flashing missing between the deck and the house.  Flashing should be added to this area to prevent water damage.
2.4 Picture 1 Missing flashing
2.5 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)
Comments: Repair or Replace
There is a negative slope towards the front of the home and the right side (facing front) of the home. This area does not appear to drain water away from home and needs to have the landscaping and drainage corrected.
2.5 Picture 1 Front
2.5 Picture 2 Side
Top Table of Contents Bottom
Foundation:
Poured concrete
Floor Structure:
Wood joists
Wall Structure:
2 X 4 Wood
Columns or Piers:
Steel screw jacks
   
Inspection Items
3.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
Comments: Inspected

There is a wood block in the east foundation wall.  Although no water damage was observed on the corresponding interior basement wall, this area should be monitored for moisture intrusion to the basement.
3.0 Picture 1
3.1 WALLS (Structural)
Comments: Inspected
3.2 COLUMNS OR PIERS
Comments: Inspected
3.3 FLOORS (Structural)
Comments: Inspected
3.4 CEILINGS (structural)
Comments: Inspected
Top Table of Contents Bottom
The inspector shall inspect: The heating system and describe the energy source and heating method using normal operating controls. And report as in need of repair electric furnaces which do not operate. And report if inspector deemed the furnace inaccessible. The central cooling equipment using normal operating controls.

The inspector is not required to: Inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers, dehumidifiers, electronic air filters, solar heating systems, solar heating systems or fuel tanks. Inspect underground fuel tanks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. Light or ignite pilot flames. Activate heating, heat pump systems, or other heating systems when ambient temperatures or when other circumstances are not conducive to safe operation or may damage the equipment. Override electronic thermostats. Evaluate fuel quality. Verify thermostat calibration, heat anticipation or automatic setbacks, timers, programs or clocks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. Inspect window units, through-wall units, or electronic air filters. Operate equipment or systems if exterior temperature is below 15 degrees Celsius or when other circumstances are not conducive to safe operation or may damage the equipment. Inspect or determine thermostat calibration, heat anticipation or automatic setbacks or clocks. Examine electrical current, coolant fluids or gasses, or coolant leakage.

Heat Type:
Circulating boiler
Energy Source:
Natural gas
Number of Heat Systems (excluding wood):
One
Inspection Items
4.0 HEATING EQUIPMENT
Comments: Inspected
4.1 NORMAL OPERATING CONTROLS
Comments: Inspected
4.2 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: Repair or Replace
(1) The heating radiator in the master bedroom ensuite has missing covers.  Covers should be installed for safety.
4.2 Picture 1 Missing cover
(2) The heating radiator in the garage has a missing cover.  A cover should be installed for safety. 
4.2 Picture 2 Missing cover
4.3 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
Comments: Inspected
4.4 CHIMNEYS, FLUES AND VENTS (for gas water heaters or heat systems)
Comments: Repair or Replace
The heating system is drawing combustion air from inside the house.  Combustion air should be supplied from outside.  This should be corrected by a qualified contractor.
Top Table of Contents Bottom
The inspector shall: Verify the presence of and identify the location of the main water shutoff valve. Inspect the water heating equipment, including combustion air, venting, connections, energy sources, seismic bracing, and verify the presence or absence of temperature-pressure relief valves and/or Watts 210 valves. Flush toilets. Run water in sinks, tubs, and showers. Inspect the interior water supply including all fixtures and faucets. Inspect the drain, waste and vent systems, including all fixtures. Describe any visible fuel storage systems. Inspect the drainage sump pumps testing sumps with accessible floats. Inspect and describe the water supply, drain, waste and main fuel shut-off valves, as well as the location of the water main and main fuel shut-off valves. Inspect and determine if the water supply is public or private. Inspect and report as in need of repair deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously. Inspect and report as in need of repair deficiencies in installation and identification of hot and cold faucets. Inspect and report as in need of repair mechanical drain-stops that are missing or do not operate if installed in sinks, lavatories and tubs. Inspect and report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak, or have tank components which do not operate.

The inspector is not required to: Light or ignite pilot flames. Determine the size, temperature, age, life expectancy or adequacy of the water heater. Inspect interiors of flues or chimneys, water softening or filtering systems, well pumps or tanks, safety or shut-of valves, floor drains, lawn sprinkler systems or fire sprinkler systems. Determine the exact flow rate, volume, pressure, temperature, or adequacy of the water supply.
Determine the water quality or potability or the reliability of the water supply or source. Open sealed plumbing access panels. Inspect clothes washing machines or their connections. Operate any main, branch or fixture valve. Test shower pans, tub and shower surrounds or enclosures for leakage. Evaluate the compliance with local or state conservation or energy standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. Determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices. Determine whether there are sufficient clean-outs for effective cleaning of drains. Evaluate gas, liquid propane or oil storage tanks. Inspect any private sewage waste disposal system or component of. Inspect water treatment systems or water filters. Inspect water storage tanks, pressure pumps or bladder tanks. Evaluate time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. Evaluate or determine the adequacy of combustion air. Test, operate, open or close safety controls, manual stop valves and/or temperature or pressure relief valves. Examine ancillary systems or components, such as, but not limited to, those relating to solar water heating, hot water circulation.

Water Source:
Well or Spring
Water Filters:
Sediment filter
Plumbing Water Supply (into home):
Copper
Galvanized (old)
PVC
Plumbing Water Distribution (inside home):
Copper
Plumbing Waste:
ABS
Water Heater Power Source:
Gas (quick recovery)
Water Heater Capacity:
40 Gallon (1-2 people)
Extra Info : 151 L
Water Heater Location:
Basement
 
Inspection Items
5.0 MAIN WATER SHUT-OFF DEVICE (Describe location)
Comments: Inspected

The main shut off is located in the basement.
5.1 PLUMBING DRAIN, WASTE AND VENT SYSTEMS
Comments: Inspected
5.2 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Comments: Repair or Replace
(1) There are shutoff valves missing under sinks.  Shutoff valves should be installed by a qualified plumber.

Low water pressure was observed throughout the house.


(2) There is no caulking around the sink in the main floor bathroom.
5.2 Picture 1 No caulking

(3) The corner between the tub and the floor in the second floor bathroom should be caulked to prevent moisture damage.
5.2 Picture 2
5.3 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS
Comments: Repair or Replace
(1) The extension for the TPR valve is missing.  This should be repaired by a qualified contractor.
5.3 Picture 1

(2) The water heater flue connection is duct taped to the main boiler flue.  This should be repaired by a qualified contractor to prevent carbon monoxide leakage.
5.3 Picture 2
5.4 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks)
Comments: Inspected
5.5 MAIN FUEL SHUT OFF (Describe Location)
Comments: Inspected

The main fuel shut off is at gas meter outside.  The gas meter is located at the north side of the house.
Top Table of Contents Bottom
The inspector shall inspect: The service line. The meter box. The main disconnect. And determine the rating of the service amperage. Panels, breakers and fuses. The service grounding and bonding. A representative sampling of switches, receptacles, light fixtures, AFCI receptacles and test all GFCI receptacles and GFCI circuit breakers observed and deemed to be GFCI's during the inspection. And report the presence of solid conductor aluminum branch circuit wiring if readily visible. And report on any GFCI-tested receptacles in which power is not present, polarity is incorrect, the receptacle is not grounded, is not secured to the wall, the cover is not in place, the ground fault circuit interrupter devices are not properly installed or do not operate properly, or evidence of arcing or excessive heat is present. The service entrance conductors and the condition of their sheathing. The ground fault circuit interrupters observed and deemed to be GFCI's during the inspection with a GFCI tester. And describe the amperage rating of the service. And report the absence of smoke detectors. Service entrance cables and report as in need of repair deficiencies in the integrity of the insulation, drip loop, or separation of conductors at weatherheads and clearances.

The inspector is not required to: Insert any tool, probe or device into the main panel, sub-panels, downstream panel, or electrical fixtures. Operate electrical systems that are shut down. Remove panel covers or dead front covers if not readily accessible. Operate over current protection devices. Operate non-accessible smoke detectors. Measure or determine the amperage or voltage of the main service if not visibly labeled. Inspect the alarm system and components. Inspect the ancillary wiring or remote control devices. Activate any electrical systems or branch circuits which are not energized. Operate overload devices. Inspect low voltage systems, electrical de-icing tapes, swimming pool wiring or any time-controlled devices. Verify the continuity of the connected service ground. Inspect private or emergency electrical supply sources, including but not limited to generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. Inspect spark or lightning arrestors. Conduct voltage drop calculations. Determine the accuracy of breaker labeling.

Electrical Service Conductors:
Overhead service
Aluminum
220 volts
Panel capacity:
200 AMP
Panel Type:
Circuit breakers
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex
 
Inspection Items
6.0 SERVICE ENTRANCE LINES
Comments: Inspected
6.1 METER BOX, MAIN DISCONNECT, SERVICE GROUNDING/BONDING and MAIN and DISTRIBUTION PANELS
Comments: Repair or Replace
The grounding wire at the meter is damaged.  Recommend repairs by a qualified electrician.
6.1 Picture 1
6.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Comments: Inspected
6.3 SWITCHES, RECEPTACLES, LIGHT FIXTURES and VISIBLE WIRING (observed from a representative number)
Comments: Repair or Replace
(1) The master ensuite outlet has reverse polarity. This should be repaired by a qualified licensed electrician. 
6.3 Picture 1
(2) Loose wire ends need to be placed inside a box with a cover-plate overhead in the garage. A qualified licensed electrician should perform repairs that involve wiring.
6.3 Picture 2
6.4 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments: Inspected
6.5 OPERATION OF GFCI or AFCI (GROUND/ARC FAULT CIRCUIT INTERRUPTERS)
Comments: Repair or Replace
GFCI (Ground Fault Circuit Interrupter) outlets at the Exterior, Garage, and Kitchen of the home are not present. While this was acceptable when this house was built, the existing outlets should be GFCI protected for safety.  A qualified licensed electrician should correct as needed.

GFCI (Ground Fault Circuit Interrupter) outlets are not present in the Bathrooms. This is a safety issue that needs to be corrected. A qualified licensed electrician should correct as needed.

6.6 LOCATION OF MAIN AND DISTRIBUTION PANELS
Comments: Inspected

The main panel box is located in the basement.
6.7 SMOKE DETECTORS
Comments: Repair or Replace
  • Detectors are noted as present but not sounded or inspected.
  • Recommend installation of new smoke detectors at each level and bedroom of the home. Placement should be in accordance with the manufacturer's recommendations.
  • Recommend the replacement of smoke detectors at 10 year intervals per the manufacturer's recommendations.
6.8 CARBON MONOXIDE DETECTORS
Comments: Repair or Replace
  • Recommend the installation of Carbon Monoxide (CO) detectors in homes with Gas/Oil fired appliances.  Placement should be in accordance with the manufacturer's recommendations.
  • Recommend the installation of Carbon Monoxide (CO) detectors in homes with attached garages.  Placement should be in accordance with the manufacturer's recommendations.
Top Table of Contents Bottom
Types of Fireplaces:
Solid Fuel
Operable Fireplaces:
One
Number of Woodstoves:
One
Inspection Items
7.0 CHIMNEYS, FLUES AND VENTS (for fireplaces)
Comments: Inspected

(1) Chimneys, flues, and vents should be inspected by a WETT certified chimney sweep before use.

(2) I do not inspect the woodstove liner because often it would require disassembly of vent pipe either at Woodstove or vent hood on roof. Also, black powder dust is expected and should be cleaned from inner walls of liner in order to properly inspect for breaks or loose sections. I recommend a qualified chimney sweep clean and inspect for safety.
7.1 SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove)
Comments: Inspected

Solid fuel heating devices such as fireplaces and woodstoves should be inspected by a WETT certified chimney sweep before use.
Top Table of Contents Bottom
The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

The inspector shall: Open and close a representative number of doors and windows. Inspect the walls, ceilings, steps, stairways, and railings. Inspect garage doors and garage door openers by operating first by remote (if available) and then by the installed automatic door control. And report as in need of repair any installed electronic sensors that are not operable or not installed at proper heights above the garage door. And report as in need of repair any door locks or side ropes that have not been removed or disabled when garage door opener is in use. And report as in need of repair any windows that are obviously fogged or display other evidence of broken seals.

The inspector is not required to: Inspect paint, wallpaper, window treatments or finish treatments. Inspect central vacuum systems. Inspect safety glazing. Inspect security systems or components. Evaluate the fastening of countertops, cabinets, sink tops and fixtures, or firewall compromises. Move furniture, stored items, or any coverings like carpets or rugs in order to inspect the concealed floor structure. Move drop ceiling tiles. Inspect or move any household appliances. Inspect or operate equipment housed in the garage except as otherwise noted. Verify or certify safe operation of any auto reverse or related safety function of a garage door. Operate or evaluate security bar release and opening mechanisms, whether interior or exterior, including compliance with local, state, or federal standards. Operate any system, appliance or component that requires the use of special keys, codes, combinations, or devices. Operate or evaluate self-cleaning oven cycles, tilt guards/latches or signal lights. Inspect microwave ovens or test leakage from microwave ovens. Operate or examine any sauna, steam-jenny, kiln, toaster, ice-maker, coffee-maker, can-opener, bread-warmer, blender, instant hot water dispenser, or other small, ancillary devices. Inspect elevators. Inspect remote controls. Inspect appliances. Inspect items not permanently installed. Examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa, recreational equipment or self-contained equipment. Come into contact with any pool or spa water in order to determine the system structure or components. Determine the adequacy of spa jet water force or bubble effect. Determine the structural integrity or leakage of a pool or spa.

Ceiling Materials:
Drywall
Ceiling Tile
Wall Material:
Drywall
Paneling
Tile
Floor Covering(s):
Carpet
Hardwood T&G
Linoleum
Interior Doors:
Hollow core
Wood
Window Types:
Casement
Cabinetry:
Wood
Countertop:
Laminate
   
Inspection Items
8.0 CEILINGS
Comments: Repair or Replace
There is evidence of water damage on the ceiling around the whole house fan filter.
8.0 Picture 1 Ceiling moisture damage
8.1 WALLS
Comments: Inspected
8.2 FLOORS
Comments: Inspected
8.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments: Inspected
8.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
Comments: Inspected
8.5 DOORS (REPRESENTATIVE NUMBER)
Comments: Inspected
8.6 WINDOWS (REPRESENTATIVE NUMBER)
Comments: Inspected
Top Table of Contents Bottom
Attic Insulation:
Unknown
Ventilation:
Soffit Vents
Exhaust Fans:
Fan/Heat/Light
Dryer Power Source:
220 Electric
   
Inspection Items
9.0 INSULATION IN ATTIC
Comments: Not Inspected

The attic access was blocked and therefore the attic was not inspected.
9.1 VENTILATION OF ATTIC AND FOUNDATION AREAS
Comments: Inspected
9.2 VENTING SYSTEMS (Kitchens, baths and laundry)
Comments: Repair or Replace
No ventilation (window or exhaust fan) for second floor bath or master bath. Normally an exhaust fan or a window is needed for proper ventilation. I recommend repair as desired.
9.3 VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC)
Comments: Repair or Replace
Whole house fan does not operate.  This system should be inspected by a qualified contractor.
Top Table of Contents Bottom
Garage Door Type:
One automatic
Garage Door Material:
Fiberglass
Insulated
Auto-opener Manufacturer:
STEEL-CRAFT
1/2 HORSEPOWER
Inspection Items
10.0 GARAGE CEILINGS
Comments: Repair or Replace
The drywall on the ceiling reveals water stains indicating a leak existed in the garage. The repair cost should be considered due to the amount of damage. A qualified contractor should inspect and repair as needed.
10.0 Picture 1
10.1 GARAGE WALLS (INCLUDING FIREWALL SEPARATION)
Comments: Inspected
10.2 GARAGE FLOOR
Comments: Inspected
10.3 GARAGE DOOR (S)
Comments: Inspected
10.4 OCCUPANT DOOR FROM GARAGE TO INSIDE HOME
Comments: Repair or Replace
The occupant door from inside garage to inside the home is not a fire rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. This door should be replaced with a fire rated door.
10.5 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance)
Comments: Inspected
Top Table of Contents Bottom
Dishwasher Brand:
KITCHENAID
Disposer Brand:
IN SINK ERATOR
Exhaust/Range hood:
VENTED
Range/Oven:
GENERAL ELECTRIC
Built in Microwave:
GENERAL ELECTRIC
 
Inspection Items
11.0 DISHWASHER
Comments: Inspected
11.1 RANGES/OVENS/COOKTOPS
Comments: Inspected
11.2 RANGE HOOD
Comments: Inspected
11.3 FOOD WASTE DISPOSER
Comments: Inspected
11.4 MICROWAVE COOKING EQUIPMENT
Comments: Inspected

Prepared Using HomeGauge
http://www.homegauge.com SHGI (c) 2000-2008 : Licensed To Welcome Home Inspections
Top Table of Contents Bottom
 

General Summary


Welcome Home Inspections

RR 2
Millet, Alberta T0C 1Z0

Phone: 780-628-4845
Cell: 780-387-1090
Email: tyler@welcomeinspections.com
Web: www.welcomeinspections.com

Customer
Sample Customer

Address
Address
City AB Postal Code

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roof
1.0   ROOF COVERINGS  
  Repair or Replace  
There is a broken shake on the first story roof on the front of the house. There are also exposed roofing nails that should be sealed with roofing tar.  These defects should be inspected and repaired by a qualified contractor.
1.1   FLASHINGS  
  Repair or Replace  
There is flashing missing between the roof and wall on the front of the house.  This can allow moisture intrusion and damage to the sheathing.  This should be inspected and repaired by a qualified contractor.
1.2   SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS  
  Repair or Replace  
There is a hole cut in the chimney cap.  This should be inspected and repaired by a qualified contractor.

A stainless steel chase cover is recommended to prevent further deterioration to the chimney crown.  This should be installed by a qualified contractor.


2.  Exterior
2.0   SIDING, FLASHING AND TRIM  
  Repair or Replace  
(1) The area between the rear patio door and bricks needs to be re-caulked to prevent moisture intrusion.
  Repair or Replace  
(2) Weep holes were observed spaced throughout the bottom course of brick around the house. Ensure these holes always remain unobstructed to allow for moisture drainage.
2.2   DOORS (Exterior)  
  Repair or Replace  
(1) The rear entry door is torn or damaged. Further deterioration may occur if not repaired. I recommend repair as desired.
  Repair or Replace  
(2) The paint has pealed on the rear door to the garage and other exterior doors.  Recommend repainting.
2.3   WINDOWS  
  Repair or Replace  
The paint and caulking around many of the windows is deteriorated.  The trim should be repainted and the edges re-caulked.
2.4   DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS  
  Repair or Replace  
There is flashing missing between the deck and the house.  Flashing should be added to this area to prevent water damage.
2.5   VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)  
  Repair or Replace  
There is a negative slope towards the front of the home and the right side (facing front) of the home. This area does not appear to drain water away from home and needs to have the landscaping and drainage corrected.

4.  Heating and Cooling
4.2   DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)  
  Repair or Replace  
(1) The heating radiator in the master bedroom ensuite has missing covers.  Covers should be installed for safety.
  Repair or Replace  
(2) The heating radiator in the garage has a missing cover.  A cover should be installed for safety. 
4.4   CHIMNEYS, FLUES AND VENTS (for gas water heaters or heat systems)  
  Repair or Replace  
The heating system is drawing combustion air from inside the house.  Combustion air should be supplied from outside.  This should be corrected by a qualified contractor.

5.  Plumbing
5.2   PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES  
  Repair or Replace  
(1) There are shutoff valves missing under sinks.  Shutoff valves should be installed by a qualified plumber.

Low water pressure was observed throughout the house.

5.3   HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS  
  Repair or Replace  
(1) The extension for the TPR valve is missing.  This should be repaired by a qualified contractor.

6.  Electrical
6.1   METER BOX, MAIN DISCONNECT, SERVICE GROUNDING/BONDING and MAIN and DISTRIBUTION PANELS  
  Repair or Replace  
The grounding wire at the meter is damaged.  Recommend repairs by a qualified electrician.
6.3   SWITCHES, RECEPTACLES, LIGHT FIXTURES and VISIBLE WIRING (observed from a representative number)  
  Repair or Replace  
(1) The master ensuite outlet has reverse polarity. This should be repaired by a qualified licensed electrician. 
  Repair or Replace  
(2) Loose wire ends need to be placed inside a box with a cover-plate overhead in the garage. A qualified licensed electrician should perform repairs that involve wiring.
6.5   OPERATION OF GFCI or AFCI (GROUND/ARC FAULT CIRCUIT INTERRUPTERS)  
  Repair or Replace  
GFCI (Ground Fault Circuit Interrupter) outlets at the Exterior, Garage, and Kitchen of the home are not present. While this was acceptable when this house was built, the existing outlets should be GFCI protected for safety.  A qualified licensed electrician should correct as needed.

GFCI (Ground Fault Circuit Interrupter) outlets are not present in the Bathrooms. This is a safety issue that needs to be corrected. A qualified licensed electrician should correct as needed.

6.7   SMOKE DETECTORS  
  Repair or Replace  
  • Detectors are noted as present but not sounded or inspected.
  • Recommend installation of new smoke detectors at each level and bedroom of the home. Placement should be in accordance with the manufacturer's recommendations.
  • Recommend the replacement of smoke detectors at 10 year intervals per the manufacturer's recommendations.
6.8   CARBON MONOXIDE DETECTORS  
  Repair or Replace  
  • Recommend the installation of Carbon Monoxide (CO) detectors in homes with Gas/Oil fired appliances.  Placement should be in accordance with the manufacturer's recommendations.
  • Recommend the installation of Carbon Monoxide (CO) detectors in homes with attached garages.  Placement should be in accordance with the manufacturer's recommendations.

8.  Doors, Windows and Interior
8.0   CEILINGS  
  Repair or Replace  
There is evidence of water damage on the ceiling around the whole house fan filter.

9.  Insulation and Ventilation
9.2   VENTING SYSTEMS (Kitchens, baths and laundry)  
  Repair or Replace  
No ventilation (window or exhaust fan) for second floor bath or master bath. Normally an exhaust fan or a window is needed for proper ventilation. I recommend repair as desired.
9.3   VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC)  
  Repair or Replace  
Whole house fan does not operate.  This system should be inspected by a qualified contractor.

10.  Garage
10.0   GARAGE CEILINGS  
  Repair or Replace  
The drywall on the ceiling reveals water stains indicating a leak existed in the garage. The repair cost should be considered due to the amount of damage. A qualified contractor should inspect and repair as needed.
10.4   OCCUPANT DOOR FROM GARAGE TO INSIDE HOME  
  Repair or Replace  
The occupant door from inside garage to inside the home is not a fire rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. This door should be replaced with a fire rated door.


Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2008 : Licensed To Welcome Home Inspections

Top Table of Contents Bottom
 

Welcome Home Inspections

RR 2
Millet, Alberta T0C 1Z0

Phone: 780-628-4845
Cell: 780-387-1090
Email: tyler@welcomeinspections.com
Web: www.welcomeinspections.com

Report Attachments

ATTENTION: This inspection report is incomplete without reading the information included herein at these links/attachments. Note If you received a printed version of this page and did not receive a copy of the report through the internet please contact your inspector for a printed copy of the attachments

Top Table of Contents Bottom
 

Welcome Home Inspections

Tyler Knelsen, C.E.T.

RR 2
Millet, Alberta T0C 1Z0

Phone: 780-628-4845
Cell: 780-387-1090
Email: tyler@welcomeinspections.com
Web: www.welcomeinspections.com

 

Top Table of Contents Bottom
 

Inspection Agreement

This inspection was performed in accordance with and under the terms of a Pre-Inspection Agreement. The agreement was signed and agreed upon before the preparation of this report and a signed copy of the agreement is available upon request.

Top Table of Contents Bottom